Header Ads Widget

Methods to Reduce Errors in Current Transformers:

 2) Leakage reactance:

Leakage reactance tends to increase ratio error. Therefore, the two windings, primary and

secondary should be close together to reduce the secondary winding leakage reactance. Use

of ring shaped cores around which toroidal windings are uniformly distributed also leads to

low values of leakage flux, leakage reactance.


3) Turns compensation:



The ratio error can be considerably reduced by using turns compensation which is almost

used in practice. This involves making secondary turns one or two less than that the number

which would make turns ration equal to nominal ratio.

We have, actual, transformation ratio :
R = n + Iw / Is

Thus if we make the "nominal ratio" equal to the turns ratio the actual transformation ratio

becomes more than the nominal ratio. Now if we reduce the turns ratio and keep the

nominal ratio equal to the earlier value, the actual transformation ratio will be reduced.This

would make actual transformation ratio nearly equal to the nominal ratio.Let us make it

clear with the help of an example.
For example, in a 1000/5A current transformer of the bar primary type is of single turn

primary, the number of turns on the secondary would be either 199 or 198 instead of 200.

The phase angle error, however, will remain almost unaffected by a slight change in the

number of turns.

4) Primary winding current ratings:



Whatever equipment a current transformer is feeding, it is desirable that the ratio of

exciting current to primary current should be small. This means that the ratio of excitation

mmf to primary winding mmf should be low. It is difficult to achieve this condition if the

latter quantity (primary winding current or mmf) is small, at low values of Ip ( or Is) , the

exciting current component Im and Iw are greater proportion of Ip and therefore, the errors
are greater.
An improvement in performance is always obtained by increasing the primary winding mmf.


5) Use of shunts:


If the secondary winding current is too large, it may be reduced by a shunt placed across the

primary or the secondary winding. This method makes an exact correction only for a

particular value and type of burden. It also reduces phase angle error.


6) Wilson compensation method:



Reduction of one or two turns of the secondary winding, no doubt, reduces the ratio error,

but it has no effect on the phase angle error. Also, this method is too coarse a method for

ratio adjustment and therefore we must use a method which exercises a finer control, say

which is equivalent to reduction to a fraction of a turn. A compensated type of design was

given by S. Wilson of the General Electric Company. This method gives finer adjustments.

It employs a few turns of wire called auxiliary secondary turns passed through a hole in the

core and connected in series with the secondary winding. A short-circuited turn is placed

around one position of the core to improve the phase relationships.

7) Two stage design:


This design utilizes a second current transformer to correct the error in secondary current

of first transformer. This method, in general, is applicable to an energy meter because a

second coil is needed in the meter to carry the error-correcting current unless an auxiliary

transformer is used.






Post a Comment

0 Comments