In an electrical power substation, Capacitor Voltage Transformer in combination with Wave
Trap is placed at the sending and receiving ends of the substation. Capacitor is behaving as
coupling capacitor. The carrier equipment is connected to the transmission line through
coupling capacitor which is of such capacitance that it offers low reactance (Xc =
1
2πfcC
) to
the carrier frequency (PLCC signal). This coupling capacitor allows carrier frequency signals
to enter the carrier equipment but does not allow 50Hz power frequency currents to enter
the carrier equipment. To reduce impedance further, low inductance is connected is
connected in series with coupling capacitor to form a resonance at carrier frequency.
Accuracy Class:
Measuring voltage transformers
Standard accuracy class may be one of 0.1, 0.2, 0.5, 1 or 3. The recommended class of
accuracy will depend upon the type of metering.
Protection voltage transformers
Generally, a measuring voltage transformer may also be used for the purpose of protection.
A protection transformer, however, is assigned an accuracy class of 3 or 6, which defines
the highest permissible percentage voltage error at any voltage between 5% of the rated
voltage up to the voltage obtained by multiplying the rated voltage by the rated voltage
factor of 1.2, 1.5 or 1.9. And when the secondary has a burden between 25% and 100% of
the rated burden at a p.f. of 0.8 lagging.
This accuracy class is followed by a letter ‘P’ such as 3P and 6P etc.
Burdens
The standard ratings, at 0.8 p.f. lagging, may be 10, 15, 25, 30, 50, 75, 100, 150, 200, 300, 400 or 500 VA / phase or
as the auxiliary circuit may demand. This is the maximum burden the transformer may have to feed at a time
Specifications
• Rated primary voltage
• Rated secondary voltage [110V or 110/√3]
• Rated frequency
• Rated burden /phase (VA) [ 100VA for 33kV; 300/500 VA for 132kV]
• Accuracy class; Measuring voltage transformers 0.1, 0.2, 0.5, 1 or 3 and Protection
voltage transformers 3P and 6P etc.
• Rated voltage factor: 1.2 Continuous, 1.5/1.9 for 30 sec/ 8 hours,
• Voltage error or ratio error
• Phase displacement error
• Basic Insulation Level (BIL)
Precautions.
The primary circuit of the PT is always to be protected by high voltage fuses. The secondary circuit is
always be protected by a low voltage fuse.
It is essential, as a safe measure, to earth the secondary circuit effectively at one point. The frame of
PT should also be earthed.
Proper attention should also be given to the polarity markings of the PT so that while making
connection to wattmeter, kWh meter, power factor meter or to the protective relays where both the
current and voltage signals are required for actuation.
0 Comments