Burden of CT:
The total load connected to the CT secondary terminal is called “burden”.
This is the value of the impedance of the secondary circuit (the impedance of all the devices
connected to it), expressed in ohms and power-factor or volt-amperes, at the rated
secondary current and frequency.
Precaution measures:
It should be noted that the secondary of the CT should not be kept open while the primary is
energized. If the secondary is left open, the secondary current becomes zero i.e. secondary
demagnetising ampere-turn disappears. Actually under normal operating condition in an
ordinary transformer the secondary ampere turns (demagnetising ampere-turn) opposes
the primary ampere turns (magnetising ampere-turn).In case of CT primary ampere-turn is
the fixed quantity. Hence, the full primary ampere-turn now become active produce very
large magnetic flux in the core as there is no counter secondary mmf. This results more core
losses and thereby increases the heat of the core. In addition, this causes to induce high
EMFs on secondary side leads to damage the insulation and an electric shock to the
attending personnel. Apart from the above, when power is removed for the circuit, this high
magnetising force leave behind an appreciable amount of residual magnetism in the core
which causes the ratio and phase angle error to differ considerably from the before.
Hence it is very important that the secondary must be connected in series with low
resistance current coils of the instruments or simply shorted. And also, for simplify the
insulation problem of the instrument and makes it safe to handle one end of the secondary
side must be connected to the ground. In practice, CTs are provided with a short circuit
switch at the secondary terminals.
0 Comments